Parameter list, Parameters a - 2, Initialization – Yaskawa P7B Drive Bypass User Manual
Page 220: User parameters

Parameters A - 2
Parameter List
Table 1: Parameter List
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Initialization
A1-00
!
Language Selection
Select Language
Language selection for digital operator display.
0: English 
1: Japanese 
2: Deutsch 
3: Francais 
4: Italiano 
5: Espanol 
6: Portugues
*Not returned to factory setting by initialization
0 to 6
0
Quick Setting
A1-01
!
Access Level Selection
Access Level
This setting determines which parameters are accessible.
0: Operation Only
1: User Level
2: Advanced Level 
0 to 2
2
Programming
A1-03
Initialize Parameters
Init Parameters
Used to return all parameters to their factory or user setting.
0: No Initialize 
1110: User Initialize (The user must set their own parameter 
default values and then parameter o2-03 must be set to “1” to save 
them. If the parameter values are changed after o2-03 is set to “1”, 
the user default values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
0 to
3330
0
Programming
A1-04
Password 1 
Enter Password
When the value set into A1-04 does NOT match the value set into 
A1-05, parameters A1-01 thru A1-03 and A2-01 thru A2-32 cannot 
be changed. All other parameters as determined by A1-01 can be 
changed. Parameter A1-05 can be accessed by pressing the MENU 
key while holding the RESET key. 
0 to 9999
0
Programming
A1-05
Password 2 
Select Password
0 to 9999
0
Programming
User Parameters
A2-01
User Parameter 1
User Param 1
Selects the parameters to be available in the User Access Level 
(A1-01 = 1). These are the only parameters accessible for the user 
level. These parameters are not related to the User Initialize 
function.
b1-01
to
o3-02
–
Programming
A2-02
User Parameter 2
User Param 2
–
Programming
A2-03
User Parameter 3
User Param 3
–
Programming
A2-04
User Parameter 4
User Param 4
–
Programming
A2-05
User Parameter 5
User Param 5
–
Programming
A2-06
User Parameter 6
User Param 6
–
Programming
!Denotes that parameter can be changed when the Drive is running.