Parameters A - 13
H1-03
Terminal S5 Function
Selection
Terminal S5 Sel
12: Forward Jog
 Closed = Drive runs forward at speed command entered into 
parameter d1-17.
13: Reverse Jog
 Closed = Drive runs in reverse at speed command entered into
parameter d1-17.
14: Fault Reset
 Closed = Resets the Drive after the fault and the run 
 command have been removed. 
15: Fast-Stop N.O.
 Closed = Drive decelerates using C1-09, regardless of run 
command status.
17: Fast-Stop N.C.
 Closed = Normal operation
 Open = Drive decelerates using C1-09, regardless of run 
command status.
18: Timer Function
 Input for independent timer, controlled by b4-01 and b4-02.
 Used in conjunction with a multi-function digital output.
19: PI Disable
 Turns off the PI controller, and PI setpoint becomes speed 
command.
1B: Program Lockout
 Closed =All parameter settings can be changed.
 Open = Only speed command at U1-01 can be changed.
1C: TrimCtl Increase
 Closed = Increase motor speed by value in d4-02.
 Open = Return to normal speed command.
 Not effective when using d1-01 thru d1-04 as a speed 
command.
 Must be used in conjunction with Trim Ctrl Decrease.
1D: Trim Ctl Decrease
 Closed = Decrease motor speed by value in d4-02.
 Open = Return to normal speed command.
 Not effective when using d1-01 thru d1-04 as speed command.
 Must be used in conjunction with Trim Ctrl Increase.
0 to 6E
3: 2-wire
0: 3-wire
Programming
Table 1: Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu