Diagnostic & troubleshooting 6 - 7 – Yaskawa P7B Drive Bypass User Manual
Page 187

Diagnostic & Troubleshooting 6 - 7
OC
Over Current
Overcurrent
Drive output current exceeded the 
overcurrent detection level (approximately 
180% of Drive rated output current).
Shorted Drive output phase to 
phase, shorted motor, locked 
rotor, load too heavy, accel/
decel time too short, contactor 
on the Drive output is opened 
and closed, a special motor or 
a motor with a FLA rating 
larger than Drive rated output 
current.
Remove the motor and run the 
Drive without the motor.
Check the motor for a phase-to-
phase short.
Check the Drive for a phase-to-
phase short at the output.
Verify C1-01 and C1-02 are set 
correctly.
Check load conditions.
OH1
Heatsnk MAX Temp
Cooling Fin/Cooling Fin Fan Overheat
The temperature of the Drive cooling fin
exceeded the temperature programmed in 
parameter L8-02.
Cooling fan(s) are not 
working, high ambient 
temperature, a heat source is 
too close to the Drive.
Check for dirt build-up on the 
fans and cooling fins.
Reduce the ambient temperature 
around the Drive.
Drive Internal Cooling Fan
Remove the heating unit.
OH3
Motor Overheat 1
Motor Overheating Alarm
The Drive stops or continues operation 
according to the setting of L1-03.
Overheating of motor as
measured by motor thermistor.
Recheck the cycle time and the 
size of the load.
Recheck the accel/decel time 
(C1-01 and C1-02).
Recheck the V/F pattern (E1-01 
thru E1-13).
Recheck the motor rated current 
value (E2-01).
OH4
Motor Overheat 2
Motor Overheating Fault
The Drive stops operation according to the 
setting of L1-04.
Overheating of motor as
measured by motor thermistor.
Recheck the cycle time and the 
size of the load.
Recheck the accel/decel time 
(C1-01 and C1-02).
Recheck the V/F pattern (E1-01 
thru E1-13).
Recheck the motor rated current 
value (E2-01).
OL1
Motor Overloaded
Motor Overload
Designed to protect the motor 
Fully adjustable from parameter E2-01
The load is too large. The 
cycle time is too short at the 
accel/decel time.
Recheck the cycle time and the 
size of the load as well as the 
times set in C1-01 and C1-02.
The voltage of the V/F pattern 
is high.
Review the V/F pattern 
parameters, E1-01 thru E1-13.
Motor rated current setting is 
improper.
Check the motor rated current 
value in E2-01.
OL2
Inv Overloaded
Drive Overload
Designed to protect the Drive
The load is too large. The 
cycle time is too short at the 
accel/decel time.
Recheck the cycle time and the 
size of the load as well as the 
times set in C1-01 and C1-02.
The voltage of the V/F pattern 
is high.
Review the V/F pattern 
parameters, E1-01 thru E1-13.
The size of the Drive is small.
Change to a larger size Drive.
Table 6.1 Fault Displays and Processing
Digital
Operator Display
Description
Cause
Corrective Action