Enclosure data, Physical installation 1 - 4 – Yaskawa P7B Drive Bypass User Manual
Page 16

Physical Installation 1 - 4
Enclosure Data
Table 1.2 208V Enclosure Data
Input
Volts
HP
1
Drive
Model
CIMR-
Bypass
2
Model
Number
NEC
FLA
OL
110%
1 min
Heat
3
Loss
Watts
Enclosure Dimensions
4
NEMA 1 & NEMA 12 -FVFF
H W D
inches
Weight
5
of
Assembly
Enclosure Dimensions w/Add-on
4
NEMA 1 & NEMA 12-FVFF
H W D
inches
Weight
5
of
Assembly
+Add-on
Box
Electrical
Schematic
208
0.5
P7U22P21A
P7B_D002
2.4
2.6
68
29.48 19.06 13.66
Dimension Drawing
6
S-5542
115 lbs
43.35 19.06 13.66
Dimension Drawing
S-5543
156 lbs
P7B-00
0.75
P7U22P21A
P7B_D003
3.5
3.8
68
1
P7U22P21A
P7B_D004
4.6
5.1
78
2
P7U22P21A
P7B_D007
7.5
8.2
110
3
P7U22P21A
P7B_D010
10.6
11.7
141
5
P7U23P71A
P7B_D016
16.7
18.4
202
7.5
P7U27P51A
P7B_D024
24.2
26.6
273
10
P7U27P51A
P7B_D030
30.8
33.9
365
127 lbs
164 lbs
15
P7U20111A
P7B_D046
46.2
50.8
578
20
P7U20151A
P7B_D059
59.4
65.3
653
40.48 25.63 14.66
Dimension Drawing
7
S-5544
208 lbs
55.35 25.63 14.66
Dimension Drawing
S-5545
291 lbs
25
P7U20181A
P7B_D074
74.8
82.3
746
30
P7U20221A
P7B_D088
88.0
96.8
939
221 lbs
307 lbs
40
P7U20301A
P7B_D114
114.0
125.4
1340
50
P7U20370A
P7B_D143
143.0
157.3
1523
84.00 25.63 26.25
8
Dimension Drawing
9
S-5550
847 lbs
NOT REQUIRED
60
P7U20450A
P7B_D169
169.0
185.9
1762
943 lbs
75
P7U20550A
P7B_D211
211.0
232.1
2244
100
P7U20750A
P7B_D273
273.0
300.3
3003
1214 lbs
125
P7U20900A
P7B_D343
343.0
377.3
3296
1330 lbs
150
P7U21100A
P7B_D396
396.0
435.6
4029
1423 lbs
Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.
Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.
Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are
included in the heat loss data. Heat loss data is for the enclosure without the add-on enclosure.
Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes MCP disconnect handle.
Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.
Note 6: All standard options are available in this size enclosure except options E (RFI Filter) and K (5% Output Reactor). Options E and K require the add-on
enclosure.
Note 7: All options are available in this size enclosure except E (RFI Filter), R (3% Line Reactor), and K (5% Output Reactor). Only option E combined with
either option R or option K can be installed in the add-on enclosure. Options R and K together require an increase in the size of the P7 Bypass Enclosure.
Contact the factory if all three options are required. Options D (2 Motor “OR”) or A (2 Motor “AND”) for 30 Hp and 40 Hp require the next
size enclosure.
Note 8: Heat sink mounted externally varies the depth dimension depending on the drive size. Depth will not exceed dimension shown.
Note 9: All options are available in this size enclosure except options D (2 Motor “OR”) or A (2 Motor “AND”) for 75 Hp and 100 Hp require the next
size enclosure.