Physical installation 1 - 5 – Yaskawa P7B Drive Bypass User Manual
Page 17

Physical Installation 1 - 5
Table 1.3 240/230V Enclosure Data
Input
Volts
HP
1
Drive
Model
CIMR-
Bypass
2
Model
Number
NEC
FLA
OL
110%
1 min
Heat
3
Loss
Watts
Enclosure Dimensions
4
NEMA 1 & NEMA 12 -FVFF
H W D
inches
Weight
5
of
Assembly
Enclosure Dimensions w/Add-on
4
NEMA 1 & NEMA 12-FVFF
H W D
inches
Weight
5
of
Assembly
+Add-on
Box
Electrical
Schematic
240
0.5
P7U22P21A
P7B_A002
2.2
2.4
68
29.48 19.06 13.66
Dimension Drawing
6
S-5542
115 lbs
43.35 19.06 13.66
Dimension Drawing
S-5543
156 lbs
P7B-00
0.75
P7U22P21A
P7B_A003
3.2
3.5
68
1
P7U22P21A
P7B_A004
4.0
4.4
78
2
P7U22P21A
P7B_A006
6.8
7.5
110
3
P7U22P21A
P7B_A009
9.6
10.6
141
5
P7U23P71A
P7B_A015
15.2
16.7
202
7.5
P7U25P51A
P7B_A022
22.0
24.2
273
10
P7U27P51A
P7B_A028
28.0
30.8
365
127 lbs
164 lbs
15
P7U20111A
P7B_A042
42.0
46.2
578
20
P7U20151A
P7B_A054
54.0
59.4
653
40.48 25.63 14.66
Dimension Drawing
7
S-5544
208 lbs
55.35 25.63 14.66
Dimension Drawing
S-5545
291 lbs
25
P7U20181A
P7B_A068
68.0
74.8
746
30
P7U20221A
P7B_A080
80.0
88.0
939
221 lbs
307 lbs
40
P7U20301A
P7B_A104
104.0
114.4
1340
230
50
P7U20370A
P7B_A130
130.0
143.0
1523
84.00 25.63 26.25
8
Dimension Drawing
9
S-5550
847 lbs
NOT REQUIRED
60
P7U20370A
P7B_A154
154.0
169.4
1544
943 lbs
75
P7U20450A
P7B_A192
192.0
211.2
1860
100
P7U20750A
P7B_A248
248.0
272.8
3003
1214 lbs
125
P7U20750A
P7B_A312
312.0
343.2
3045
1330 lbs
150
P7U20900A
P7B_A360
360.0
396.0
3440
1423 lbs
Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.
Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.
Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are
included in the heat loss data. Heat loss data is for the enclosure without the add-on enclosure.
Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes MCP disconnect handle.
Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.
Note 6: All standard options are available in this size enclosure except options E (RFI Filter) and K (5% Output Reactor). Options E and K require the add-on
enclosure.
Note 7: All options are available in this size enclosure except E (RFI Filter), R (3% Line Reactor), and K (5% Output Reactor). Only option E combined with
either option R or option K can be installed in the add-on enclosure. Options R and K together require an increase in the size of the P7 Bypass Enclosure.
Contact the factory if all three options are required. Options D (2 Motor “OR”) or A (2 Motor “AND”) for 30 Hp and 40 Hp require the next size
enclosure.
Note 8: Heat sink mounted externally varies the depth dimension depending on the drive size. Depth will not exceed dimension shown.
Note 9: All options are available in this size enclosure except options D (2 Motor “OR”) or A (2 Motor “AND”) for 75 Hp and 100 Hp require the next size
enclosure.