beautypg.com

Parameters a - 18, Analog outputs, Serial com setup – Yaskawa P7B Drive Bypass User Manual

Page 236: Table 1, Parameter list (continued

background image

Parameters A - 18

Analog Outputs

H4-06

!

Terminal AM Bias Setting
Terminal AM Bias

Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 0% output.

–110.0 to

110.0

0.0%

Programming

H4-07

Terminal FM Signal Level
Selection
AO Level Select1

0: 0 - 10 VDC
2: 4-20 mA*

0 or 2

0

Programming

H4-08

Terminal AM Signal Level
Selection
AO Level Select2

0: 0 - 10 VDC
2: 4-20 mA*
* An analog output of 4 - 20 mA can not be used with
the standard terminal board. Therefore an optional ter-
minal board (with shunt connector CN15) is needed.

0 or 2

0

Programming

Serial Com Setup

H5-01

Drive Node Address
Serial Com Adr

Selects Drive station node number (address) for
terminals R+, R-, S+, S-.*
Note: An address of “0” disables serial com.

0 to FF(hex,

H5-08

dependent)

1F

Programming

H5-02

Communication Speed Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud
3: 9600 Baud
4: 19200 Baud

0 to 4

3

Programming

H5-03

Communication Parity Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-,
S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

H5-04

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication
error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Runn at D1-04

0 to 3

3

Programming

H5-05

Communication Error Detection
Selection
Serial Flt Dtct

Enables or disables the communications timeout
detection function.
0: Disabled - A communications loss will NOT cause a

communications fault.

1: Enabled - If communications are lost for more than

the time specified in parameter H5-09, a communica-
tions fault will occur.

0 or 1

1

Programming

H5-06

Drive Transmit Wait Time
Transmit WaitTIM

Sets the time from when the Drive receives data to
when the Drive sends data.

5 to 65

5ms

Programming

H5-07

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

H5-08

Communication Protocol Selec-
tion
Protocol Select

Selects the communication protocol.
0: Memobus (Modbus)

0

0

Programming

H5-09

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost
before a fault is annunciated. Works in conjunction with
parameters H5-05 and H5-04.

0.0 to 10.0

2.0sec

Programming

!Denotes that parameter can be changed when the Drive is running.
* After these parameters are changed, Drive power must be cycled before the changes will take effect.

Table 1:

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location