Yaskawa P7B Drive Bypass User Manual
Page 140

Programming 5 - 46
"
E1-05 Maximum Output Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 208.0V (208V Models)
240.0V (240V Models)
480.0V (480V Models)
"
E1-06 Base Frequency
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 60.0 Hz
"
E1-07 Mid Output Frequency A
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 3.0 Hz
"
E1-08 Mid Output Voltage A
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 18.0V (208V Models)
18.0V (240V Models)
18.0V (480V Models)
"
E1-09 Minimum Output Frequency
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 1.5 Hz
"
E1-10 Mid Output Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 10.8V (208V Models)
10.8V (240V Models)
10.8V (480V Models)
"
E1-11 Mid Output Frequency B
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 0.0 Hz
"
E1-12 Mid Output Voltage B
E1-13 Base Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 0.0V (208V Models)
0.0V (240V Models)
0.0V (480V Models)