Bypass model number and enclosure style, Physical installation 1 - 2 – Yaskawa P7B Drive Bypass User Manual
Page 14

Physical Installation 1 - 2
Bypass Model Number and Enclosure Style
The Bypass covers two voltage ranges: 208-240 VAC and 480 VAC. Ratings applicable are from 1/2 to 500 HP.
Table 1.1 Bypass
Voltage
Bypass
Base Model Number
HP
Bypass
Continuous
Output
Current
(Amps)
Uses
Basic Drive
Model
-
Number
NEMA 1
*NEMA 12
FVFF
208 VAC
P7BVD002
P7BBD002
0.5
2.4
CIMR-P7U22P2
P7BVD003
P7BBD003
0.75
3.5
CIMR-P7U22P2
P7BVD004
P7BBD004
1
4.6
CIMR-P7U22P2
P7BVD007
P7BBD007
2
7.5
CIMR-P7U22P2
P7BVD010
P7BBD010
3
10.6
CIMR-P7U22P2
P7BVD016
P7BBD016
5
16.7
CIMR-P7U23P7
P7BVD024
P7BBD024
7.5
24.2
CIMR-P7U27P5
P7BVD030
P7BBD030
10
30.8
CIMR-P7U27P5
P7BVD046
P7BBD046
15
46.2
CIMR-P7U2011
P7BVD059
P7BBD059
20
59.4
CIMR-P7U2015
P7BVD074
P7BBD074
25
74.8
CIMR-P7U2018
P7BVD088
P7BBD088
30
88
CIMR-P7U2022
P7BVD114
P7BBD114
40
114
CIMR-P7U2030
P7BVD143
P7BBD143
50
143
CIMR-P7U2037
P7BVD169
P7BBD169
60
169
CIMR-P7U2045
P7BVD211
P7BBD211
75
211
CIMR-P7U2055
P7BVD273
P7BBD273
100
273
CIMR-P7U2075
P7BVD343
P7BBD343
125
343
CIMR-P7U2090
P7BVD396
P7BBD396
150
396
CIMR-P7U2110
240 VAC
P7BVA002
P7BBA002
0.5
2.2
CIMR-P7U22P2
P7BVA003
P7BBA003
0.75
3.2
CIMR-P7U22P2
P7BVA004
P7BBA004
1
4.0
CIMR-P7U22P2
P7BVA006
P7BBA006
2
6.8
CIMR-P7U22P2
P7BVA009
P7BBA009
3
9.6
CIMR-P7U22P2
P7BVA015
P7BBA015
5
15.2
CIMR-P7U23P7
P7BVA022
P7BBA022
7.5
22
CIMR-P7U25P5
P7BVA028
P7BBA028
10
28
CIMR-P7U27P5
P7BVA042
P7BBA042
15
42
CIMR-P7U2011
P7BVA054
P7BBA054
20
54
CIMR-P7U2015
P7BVA068
P7BBA068
25
68
CIMR-P7U2018
P7BVA080
P7BBA080
30
80
CIMR-P7U2022
P7BVA104
P7BBA104
40
104
CIMR-P7U2030