Programming 5 - 39
!
d1 Preset References
"
d1-01 Frequency Reference 1
d1-02 Frequency Reference 2
d1-03 Frequency Reference 3
d1-04 Frequency Reference 4
Setting Range:
0.00 to E1-04 Value
Factory Default: d1-01 = 10.00 Hz
d1-02 = 6.00 Hz
d1-03 = 0.00 Hz
d1-04 = 40.00 Hz
d1-01, d1-02 and d1-04 are special parameter settings required by the Bypass logic circuit. See Table 5.1.
Fig 5.20 Preset Reference Timing Diagram example
"
d1-17 Jog Frequency Reference
Setting Range:
0.00 to E1-04 Value
Factory Default: 6.00 Hz
The Drive can be programmed to utilize digital inputs to change between four presets speeds and a jog speed. It is a two-step
process to set the Drive up for preset speeds. First, d1-01 through d1-04 and d1-17 must be programmed with the desired preset
speeds and the desired jog speed, respectively. Next, up to three of the Drive’s digital inputs (Terminals S3 through S7) need to be
programmed (via parameters H1-01 to H1-05) and wired (to normally open contacts) as Multi-step Speed Reference 1, Multi-step
Speed Reference 2, and Jog Frequency.
Table 5.7 Preset Speed Truth Table
Preset Speed
Terminal
programmed
as Multi-step
Reference 1
Terminal
programmed
as Multi-step
Reference 2
Terminal
programmed
as Jog
Reference
Details
1
OFF
OFF
OFF
Frequency Reference 1 (d1-01) or analog input A1
2
ON
OFF
OFF
Frequency Reference 2 (d1-02) or analog input A2
3
OFF
ON
OFF
Frequency Reference 3 (d1-03)
4
ON
ON
OFF
Frequency Reference 4 (d1-04)
5
-
-
ON*
Jog Frequency (d1-17)
*
The Jog Frequency input is given priority over the multi-step speeds.
RUN
Multi-step
Reference 1 Input
Multi-step
Reference 2 Input
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Jog Input
Output
Speed
t
d1-01
d1-02
d1-03
d1-04
d1-17