beautypg.com

1 status indication by led indicators – Yaskawa JAPMC-CM2304-E User Manual

Page 83

background image

6.1 Status Indication by LED Indicators

6-2

6.1 Status Indication by LED Indicators

The following table provides a description of the 263IF-01 Module status indicated by each LED indicator.

Œ z

: Lit, {: Not lit, : Flashing, –: Indefinite

Classification

LED Indication

Meaning

Description

MS

NS LNK TX

RX

Power ON

{

{

The power is
turned ON

The status immediately after the power is turned
ON. Module initialization processing is in progress.
After the completion of processing, the Module is
placed in the initial status.

LED Test

LED test

When Module initialization is completed, the LED
test is performed.

Self-

diagnosis



Red

Green



Red

Green

Self diagnosis in
progress

After the completion of the LED test, self-diagnosis
is performed.

Initial status



Green



Green

Waiting for initial
settings

The status in which the Module, started normally, is
waiting for initialization by the CPU.
The 100M, TX and RX indicators light according to
the connection status.

Normal

z

Green

z

Green

Operating
normally

The status in which the Module is performing
Ethernet communication normally.
The TX and RX indicators flash during Ethernet
communication.
The 100M indicator is lit during 100M communica-
tion.

Other

z

Green



Green

No connection

The status in which the device has obtained the IP
address but the connection has not been established.

Error

z

Green



Red

Connection
timeout

Timeout is detected on at least one connection
where a device is the target of connection.

z

Green

z

Red

IP address
duplication

The IP address is already being used in another
device.



Red

Minor fault status

The status in which a device has detected a recover-
able minor fault. A setting error will be the cause of
the problem.

z

Red

Major fault status

The status in which a device has detected an unre-
coverable major fault. If the error status does not
clear even if the power is shut off and turned on
again, the Module must be replaced.