Yaskawa JAPMC-CM2304-E User Manual
Page 74

5.2 Message Send Function
5.2.5 Details of Parameters Used in Explicit Message
5-12
[ a ] REQUEST
The status of the processing request for the MSG-SND function is output to this bit.
[ b ] RESULT
The result of executing MSG-SND function is output to these bits.
[ c ] COMMAND
The processing command for the MSG-SND function is output to these bits. The executed process is indicated by the
COMMAND bits.
[ d ] PARAMETER
The following error code is output if RESULT (Processing result) is set to 4 (FMT_NG: parameter format error).
In other cases, the remote connection number is output.
Bit Status
Meaning
1
Processing is being requested.
0
Processing request has been accepted.
Code Abbreviation
Meaning
1
SEND_OK
Sending has been completed normally.
2
REC_OK
Receiving has been completed normally.
3
ABORT_OK
Abort completed.
4
FMT_NG
Parameter format error
5
SEQ_NG
Command sequence error
6
RESET_NG
Reset status
7
REC_NG
Data receive error (Error detected by a lower-layer program.)
Code (Hex)
Abbreviation
Meaning
3
ABORT
Abort
8
M_SEND
Send MEMOBUS command;
execution of the command is completed upon reception of a response.
9
M_REC
Receive MEMOBUS command;
execution of the command is followed by the sending of a response.
C
MR_SEND
Send MEMOBUS response
RESULT Code
Meaning
RESULT = 4
(FMT_NG:
parameter format error)
00
No errors
01
Remote connection number out of range
02
MEMOBUS response receive monitor time error
03
Retry count setting error
04
Cyclic area setting error
05
Not used
06
Data address error
07
Data size error
08
Function code error
10H
Function code error or format conversion error
Other values of RESULT
XX
Remote connection number