Failure Search

SMA Solar Technology AG

70

SMC6-8TL-IEN101040

Installation Guide

You can check the varistors as follows:

1. Open the inverter as described in section 7.2 ”Opening the Inverter” (page 52).
2. Use a Multimeter to ensure that both varistors in the

installed state have a conducting connection
between connectors B and C.

Position of Varistors
You can determine the position of the varistors with the help of the illustration below.
Observe the following allocation of the
terminals:

• Terminal A: outer terminal (varistor

connection with loop [crimp])

• Terminal B: middle terminal
• Terminal C: outer terminal (varistor

connection without loop [crimp])

Result

Action

☑ There is a conductive connection. There is probably a different fault in the inverter.

• Close the inverter as described in section

7.3 ”Closing the Inverter” (page 55).

• Contact the SMA Serviceline (see section

13 ”Contact” (page 85)).

☑ There is no conductive

connection.

The respective varistor is defective and must be replaced.
Varistor failure is generally due to influences which affect
all varistors similarly (temperature, age, induced
overvoltage). SMA Solar Technology AG recommends
that you replace both varistors.
The varistors are specially manufactured for use in the
inverter and are not commercially available. You must
order replacement varistors directly from SMA Solar
Technology AG (see section 12 ”Accessories”
(page 84))
.

• To replace the varistors, proceed to step 3.