5.2 Connection to the public grid (AC)
5.2.1 Conditions for the AC Connection
Cable Sizing
The conductor cross-section should be dimensioned in a way that output losses do not exceed 1 % at
nominal power. Use "Sunny Design" (www.SMA.de/en/SunnyDesign) for this.
The maximum cable lengths relative to the conductor cross-section are shown in the following table.
The conductor cross-sectional area required in individual cases depends on the following factors
among others:
• Ambient temperature,
• Routing method,
• UV resistance.
F
Connections terminals for SMA Power Balancer (page 37)
G
Flat connector for grounding the cable shield when connecting the SMA Power
Balancer (page37)
H
Connection terminals for mains cable (AC) (page 23)
I
Cable glands for the SMA Power Balancer (page 37)
K
Cable gland for grid connection (AC) (page 23)
L
Cable gland for communication (page 44)
M
Screwing device of shield clamp for communication cable (page 44)
N
O
Connection socket for “Electronic Solar Switch (ESS)” DC load disconnection unit
(page 30)
P
Male connector for grounding the cable shield for communication (page 44)
Q
Varistors (page 69)
Connection requirements of the utility operator
Always observe the connection requirements of your utility operator!
Conductor cross-
section
Maximum cable length
SMC 6000TL
SMC 7000TL
SMC 8000TL
10.0 mm²
25 m
22 m
19 m
16.0 mm²
41 m
35 m
31 m
Cut line losses in half
If three inverters with symmetrical feeding are combined to form a three-phase system, the
neutral conductor is not subjected to any load, and the line losses are halved. Thus, the
maximum possible cable length is doubled.