Failure Search

SMA Solar Technology AG

66

SMC6-8TL-IEN101040

Installation Guide

ROM

The inverter's firmware is faulty.
Corrective measures

• Contact the SMA Serviceline

SD-DI-Wandler

The inverter has detected an insulation fault on the DC side.
Corrective measures

• Check the plant insulation.
• Check the plant for ground faults as described in section

9.3.1 ”Checking the PV Generator for a Ground Fault” (page 68).

SD-Imax

The inverter has detected an overcurrent on the AC side. It disconnects
from the grid for safety reasons and then attempts to reconnect to the
grid.
Corrective measures

• If this fault occurs often, contact the SMA Serviceline

SD-WR-Bruecke

The inverter has detected a fault in the power electronics. It disconnects
from the grid and then attempts to reconnect to the grid. There could also
be a ground fault in the PV generator.
Corrective measures

• Check for ground faults in the PV generator as described in section

9.3.1 ”Checking the PV Generator for a Ground Fault” (page 68).

• If this fault continues to occur, contact the SMA Serviceline

Shutdown

Temporary inverter fault.
Corrective measures

• Contact the SMA Serviceline

STM Timeout

Internal program run fault.
Corrective measures

• If this fault occurs often, contact the SMA Serviceline

Message

Description and corrective measure