SMA SMC 6000TL Installation User Manual
Page 66
Failure Search
SMA Solar Technology AG
66
SMC6-8TL-IEN101040
Installation Guide
ROM
The inverter's firmware is faulty.
Corrective measures
• Contact the SMA Serviceline
SD-DI-Wandler
The inverter has detected an insulation fault on the DC side.
Corrective measures
• Check the plant insulation.
• Check the plant for ground faults as described in section
9.3.1 ”Checking the PV Generator for a Ground Fault” (page 68).
SD-Imax
The inverter has detected an overcurrent on the AC side. It disconnects
from the grid for safety reasons and then attempts to reconnect to the
grid.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
SD-WR-Bruecke
The inverter has detected a fault in the power electronics. It disconnects
from the grid and then attempts to reconnect to the grid. There could also
be a ground fault in the PV generator.
Corrective measures
• Check for ground faults in the PV generator as described in section
9.3.1 ”Checking the PV Generator for a Ground Fault” (page 68).
• If this fault continues to occur, contact the SMA Serviceline
Shutdown
Temporary inverter fault.
Corrective measures
• Contact the SMA Serviceline
STM Timeout
Internal program run fault.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
Message
Description and corrective measure