8.2 Checking the Electronic Solar Switch (ESS) for Wear
Check the Electronic Solar Switch for wear before plugging it in.
NOTICE!
Risk of damage to the inverter if insects enter it!
• The air grills must not be removed permanently, because otherwise the device is not
protected against the entrance of insects!
Result
Action
☑ The metal tongues inside the connector are
not damaged or discolored.
1. Securely attach the Electronic Solar Switch
handle.
2. Re-commission the inverter as described in
section 6 ”Commissioning” (page 46).
☑ The metal tongues inside the connector
have a brown discoloration or are burned
through.
The Electronic Solar Switch can no longer reliably
disconnect the DC side.
1. Replace the Electronic Solar Switch handle
before attaching it again (for the order
number see section 12 ”Accessories”
(page 84).
2. Re-commission the inverter as described in