2 checking the functioning of the varistors, Checking the functioning of the varistors – SMA SMC 6000TL Installation User Manual

Page 69

background image

SMA Solar Technology AG

Failure Search

Installation Guide

SMC6-8TL-IEN101040

69

The approximate position of the ground fault can be determined from the ratio of the measured
voltages between plus against ground potential and minus against ground potential.
Example:

The ground fault is between the second and third module in this case.

3. Repeat step 2 for each string.

☑ The ground fault check is finished.

9.3.2 Checking the Functioning of the Varistors

Varistors are wearing parts. Their functional efficiency diminishes with age or following repeated
responses as a result of overvoltages. It is therefore possible that one of the thermally monitored
varistors has lost its protective function.

Result

Action

☑ You have found a ground fault.

• The installer of the PV generator must remedy the

ground fault in the affected string before you may
reconnect the string to the inverter.

• Do not reconnect the faulty string.
• Restart the inverter as described in section

7.3 ”Closing the Inverter” (page 55), but without
reconnecting the faulty string.

☑ You have found no ground fault. It is likely that one of the thermally monitored varistors is

defective.

• Check the varistors as described in section

9.3.2 ”Checking the Functioning of the Varistors”
(page 69)
.