beautypg.com

SMA SMC 6000TL Installation User Manual

Page 42

background image

Electrical Connection

SMA Solar Technology AG

42

SMC6-8TL-IEN101040

Installation Guide

Procedure

1. Open the inverter as described in section 7.2 ”Opening the Inverter” (page 52).
2. Insert the cable into each inverter.

Use one of the two cable glands (F) on the right hand side.

3. Draw the cable along the cable route (E) as far as the terminal block (B).
4. Ground the cable shield in each inverter to the PE connector (D).
5. Sheath the positive and negative cable conductors in each inverter with end sleeves.
6. Connect the positive and negative pole to the

corresponding screw terminals.

7. In order to connect the three inverters together, connect the positive and negative conductors

from the two other inverters to the terminal block of the middle inverter.

D

PE connector

E

Silicone tube / cable route

F

Cable glands

DANGER!
Danger to life through high voltage if there is a fault with the SMA Power
Balancer cable.

• Sheath the positive and negative cable conductors in each inverter using the

enclosed silicone tube.

• Cut the silicone tube to the required length.
• The silicone tube must completely cover the cable inside the inverter enclosure.

Object

Description

This manual is related to the following products: