Electrical Connection

SMA Solar Technology AG

24

SMC6-8TL-IEN101040

Installation Guide

Cable Requirements

Load Disconnection Unit

You must install a separate line circuit breaker for each inverter in order to ensure that the inverter
can be securely disconnected under load. The maximum permissible rating is located in section
11 ”Technical Data” (page 74).
Detailed information and examples for the rating of a line circuit breaker can be found in the Technical
Information "Line Circuit Breaker" in the SMA Solar Technology AG download area at
www.SMA.de/en.

Position

Description

Value

A

External diameter

12 mm … 25 mm

B

Conductor cross-section

10 mm² … 16 mm²

C

Strip insulation

Approx. 16 mm

DANGER!
Danger to life due to fire.

When more than one inverter is connected to the same line circuit breaker, the protective
function of the line circuit breaker is no longer guaranteed. It can result in a cable fire or
the destruction of the inverter.

• Never connect several inverters to the same line circuit breaker.
• Comply with the maximum permissible fuse protection of the inverter when selecting

the circuit breaker.