Interference suppression, 2 interference suppression – SMA Sunny Boy Control Light User Manual

Page 78

background image

Sunny Boy Control Light

Chapter 7: Appendix

SUNBCL-11:NE

- 78 -

SMA Regelsysteme GmbH

house electricity distribution

connection to

public grid

Sunny Boy

Control Light

Sunny Boy

Sunny Boy

D

Blocking

Filters

Damping

Module

interfering device

Fig.7.10: Interference suppression from several communication systems

7.2.2 Interference

Suppression

If the data transmission via Powerline is interrupted from time to time, or cannot be

established at all, the transmission line has to be cleared. For this purpose please

take the following steps:

Identification of Interference Sources

Starting point of the examination should be a functioning data transmission, if

possible. Please disconnect all electric devices from the mains (it is sometimes

not sufficient merely to switch them off! Please think also about three-phase

current consumers!) which are connected to the same line as the devices and

the Sunny Boy Control Light. Switch off all remaining fuses in the household

distribution. Now connect the Sunny Boy Control Light with an extension

cable to the socket with the shortest wiring length to the inverter. Start the

function "

Diagnosis - Communication

Diagnosis - Communication

Diagnosis - Communication

Diagnosis - Communication

" and select the device to be

monitored. Sunny Boy Control Light now tries to communicate with the device