Larger facilities: The optimal position of the phase coupler is sometimes difficult

to find. Main distribution and sub distribution are sometimes very far apart and

result in different reasonable positions of the phase coupler.

connection to

public grid

phase coupler

House electricity distribution

L1

L2

L3

sub-distribution

phase coupler

Sunny Boy

Control Light

Sunny Boy

Sunny Boy

Fig. 7.8: Phase coupling for communication over different phases

Interfering Signals on the Grid

The data transmission is done with a frequency of 132.45 kHz. If other consumers

also use this frequency, the transmission may be disturbed when a certain level is

exceeded. Interfering signals can be developed by electric devices in the own

household (insufficiently filtered switching power supply or similar), but also by

devices in neighboring houses (e.g. electric devices with high power consumption in

the neighborhood).