beautypg.com

SMA Sunny Boy Control Light User Manual

Page 73

background image

Sunny Boy Control Light

Chapter 7: Appendix

SUNBCL-11:NE

- 73 -

SMA Regelsysteme GmbH

In the following please find the most important causes for Powerline transmission

faults and an overview of possible counter-measures (interference suppression). In

case of transmission errors between Sunny Boy Control Light and the connected

devices please read this chapter first and try to find the failure source by carrying out

the steps described in chapter 7.2.2: "Interference Suppression".

Strong Damping of the Carrier Signal

Most frequently transmission errors result from carrier signal damping. The reason for

this may be a too long distance between the inverters and Sunny Boy Control Light

however, often there are electric devices connected to this cable. Devices with a high

input capacity may dampen the carrier signal strongly, and it is not necessarily

important whether the device is on or off. Examples are washing machines, electric

ranges, microwave ovens, PCs, fluorescent lamps etc.

The easiest counter-measure is to connect the respective electrical devices to

another line resp. to another phase. Another possibility is to install a special filter in

the power supply of the interfering electrical devices.

If, in extreme cases, the wiring length resp. wiring arrangement is the cause for a

disturbed communication, the installation of a separate line from the inverters to the

Sunny Boy Control Light can be necessary.