17 technical data, 1 measurement accuracy, 2 sunny central 500cp-us/ca – SMA SC 500CP-US User Manual
Page 98
![background image](https://www.manualsdir.com/files/818341/content/doc098.png)
17 Technical Data
SMA America, LLC
98
SCCP-US-IA-US_en-41
Installation Manual
17 Technical Data
17.1 Measurement Accuracy
The inverter is not equipped with a calibrated meter. The display values may deviate from the actual values and must not
be used as a basis for invoicing. The inverter’s measured values are required for the system management and to control
the current to be fed to the grid.
Deviation:
Voltage measurement: +/– 8.5 V
Frequency measurement: +/– 0.06 Hz
Disconnect time: +/–4.5%
17.2 Sunny Central 500CP-US/CA
Input Data
Output Data
Power Consumption
MPP voltage range
430 V
DC
to 820 V
DC
Maximum DC voltage
1,000 V
DC
Maximum DC current
1,600 A
DC
Max. array short circuit current
2,596 A
DC
Number of DC inputs*
* Only in the inverter option with DC fuses single phase
9
DC overvoltage category
II
Continuous AC power at +122°F (+50°C)
500 kVA
Continuous AC power at +104°F (+40°C)
520 kVA
Continuous AC power at +77°F (+25°C)
550 kVA
AC current at +122°F (+50°C)
1,069 A
AC
AC current at +104°F (+40°C)
1,112 A
AC
AC current at +77°F (+25°C)
1,167 A
AC
Nominal AC voltage ± 10%
270 V
AC
Nominal power frequency
60 Hz [50 Hz]
Power frequency range
59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]
Power factor cos φ
0.8 to 1
Current total harmonic distortion
< 5% (with respect to IEEE 1547)
AC overvoltage category
IV
Self-consumption in operation
< 1,800 W
Standby consumption
< 150 W
Control supply voltage
See nameplate in the connection area of the control circuit