9 sunny central 900cp-us/ca – SMA SC 500CP-US User Manual
Page 106

17 Technical Data
SMA America, LLC
106
SCCP-US-IA-US_en-41
Installation Manual
Dimensions and Weight
Efficiency
Ambient Conditions
17.9 Sunny Central 900CP-US/CA
Input Data
Output Data
Width x height x depth
8 ft. 4.87 in x 7 ft. 5.45 in x 3 ft. 1.64 in.
(2,562 mm x 2,272 mm x 956 mm)
Weight
4,123 lb (1,870 kg)
Maximum efficiency
98.6%
CEC-eta
98.5%
Enclosure rating outdoor
Type 3R
Enclosure rating indoor
Type 1
Operating temperature range
− 13°F to 122°F ( − 25°C to +50°C)
Maximum altitude above mean sea level, MSL
6,562 ft. (2,000 m)
Supply air flow and quality
1766 SCFM (3,000 m
3
/h), Class 4S2
MPP voltage range
655 V
DC
to 820 V
DC
Maximum DC voltage
820 V
Maximum DC current
1,600 A
DC
Max. array short circuit current
2,596 A
DC
Number of DC inputs*
* Only in the inverter option with DC fuses single phase
9
DC overvoltage category
II
Continuous AC power at +122°F (+50°C)
900 kVA
Continuous AC power at +104°F (+40°C)
936 kVA
Continuous AC power at +77°F (+25°C)
990 kVA
AC current at +122°F (+50°C)
1,283 A
AC
AC current at +104°F (+40°C)
1,334 A
AC
AC current at +77°F (+25°C)
1,411 A
AC
Nominal AC voltage ± 10%
405 V
AC
Nominal power frequency
60 Hz [50 Hz]
Power frequency range
59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]
Power factor cos φ
0.8 to 1
Current total harmonic distortion
< 5% (with respect to IEEE 1547)