17 Technical Data
Installation Manual
SCCP-US-IA-US_en-41
107
Power Consumption
Dimensions and Weight
Efficiency
Ambient Conditions
17.10 Integrated AC Disconnect
AC Disconnect Ratings
AC overvoltage category
IV
Self-consumption in operation
< 1,800 W
Standby consumption
< 150 W
Control supply voltage
See nameplate in the connection area of the control circuit
Width x height x depth
8 ft. 4.87 in x 7 ft. 5.45 in x 3 ft. 1.64 in.
(2,562 mm x 2,272 mm x 956 mm)
Weight
4,123 lb (1,870 kg)
Maximum efficiency
98.6%
CEC-eta
98.5%
Enclosure rating outdoor
Type 3R
Enclosure rating indoor
Type 1
Operating temperature range
− 13°F to 122°F ( − 25°C to +50°C)
Maximum altitude above mean sea level, MSL
6,562 ft. (2,000 m)
Supply air flow and quality
1766 SCFM (3,000 m
3
/h), Class 4S2
Compliance Standard
UL 1066
Frame Size
1600 A
Rated maximum voltage
635 V
Rated short-circuit current
42 kA
Rated short-time current
42 kA
Rated frequency
50 Hz - 60 Hz
Make time (max)
80 ms
Break time (I 70 ms Break time (I>ST current)(max) 30 ms