SMA SC 500CP-US User Manual
Page 103

SMA America, LLC
17 Technical Data
Installation Manual
SCCP-US-IA-US_en-41
103
Output Data
Power Consumption
Dimensions and Weight
Efficiency
Ambient Conditions
Maximum DC voltage
1,000 V
DC
Maximum DC current
1,600 A
DC
Max. array short circuit current
2,596 A
DC
Number of DC inputs*
9
DC overvoltage category
II
* Only in the inverter option with DC fuses single phase
Continuous AC power at +122°F (+50°C)
750 kVA
Continuous AC power at +104°F (+40°C)
780 kVA
Continuous AC power at +77°F (+25°C)
825 kVA
AC current at +122°F (+50°C)
1,266 A
AC
AC current at +104°F (+40°C)
1,317 A
AC
AC current at +77°F (+25°C)
1,393 A
AC
Nominal AC voltage ± 10%
342 V
AC
Nominal power frequency
60 Hz [50 Hz]
Power frequency range
59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]
Power factor cos φ
0.8 to 1
Current total harmonic distortion
< 5% (with respect to IEEE 1547)
AC overvoltage category
IV
Self-consumption in operation
< 1,800 W
Standby consumption
< 150 W
Control supply voltage
See nameplate in the connection area of the control circuit
Width x height x depth
8 ft. 4.87 in x 7 ft. 5.45 in x 3 ft. 1.64 in.
(2,562 mm x 2,272 mm x 956 mm)
Weight
4,123 lb (1,870 kg)
Maximum efficiency
98.62%
CEC-eta
98%
Enclosure rating outdoor
Type 3R
Enclosure rating indoor
Type 1
Operating temperature range
− 13°F to 122°F ( − 25°C to +50°C)