Ambient Conditions
17.8 Sunny Central 850CP-US/CA
Input Data
Output Data
Power Consumption
CEC-eta
98.5%
Enclosure rating outdoor
Type 3R
Enclosure rating indoor
Type 1
Operating temperature range
− 13°F to 122°F ( − 25°C to +50°C)
Maximum altitude above mean sea level, MSL
6,562 ft. (2,000 m)
Supply air flow and quality
1766 SCFM (3,000 m
3
/h), Class 4S2
MPP voltage range
620 V
DC
to 820 V
DC
Maximum DC voltage
820 V
Maximum DC current
1,600 A
DC
Max. array short circuit current
2,596 A
DC
Number of DC inputs*
* Only in the inverter option with DC fuses single phase
9
DC overvoltage category
II
Continuous AC power at +122°F (+50°C)
850 kVA
Continuous AC power at +104°F (+40°C)
884 kVA
Continuous AC power at +77°F (+25°C)
935 kVA
AC current at +122°F (+50°C)
1,271 A
AC
AC current at +104°F (+40°C)
1,322 A
AC
AC current at +77°F (+25°C)
1,399 A
AC
Nominal AC voltage ± 10%
386 V
AC
Nominal power frequency
60 Hz [50 Hz]
Power frequency range
59.3 Hz to 60.5 Hz [49.3 Hz to 50.5 Hz]
Power factor cos φ
0.8 to 1
Current THD
< 5% (with respect to IEEE 1547)
AC overvoltage category
IV
Self-consumption in operation
< 1,800 W
Standby consumption
< 150 W
Control supply voltage
See nameplate in the connection area of the control circuit