12.6 Tripping Limits/Tripping Times
Manufacturer's accuracies
Tripping limit accuracy: ±2% of nominal line voltage
Tripping time accuracy: ±0.1% of nominal tripping time
Tripping frequency accuracy: ±0.1% of nominal frequency
13 Accessories
You will find the corresponding accessories and spare parts for your product in the following
overview. If required, these can be ordered from SMA or your specialty retailer.
Nominal
frequency
Tripping limit
Tripping frequencies
Tripping times
60 Hz
˃ 60.5 Hz
60.45 Hz to 60.55 Hz
max. 0.1602 s
˂ 57.0 Hz to 59.8 Hz
(standard 59.3 Hz)
56.95 Hz to 59.85 Hz
(standard
59.25 Hz to 59.35 Hz)
Adjustable, 0.16 s to 300 s
(standard max. 0.1602 s)
˂ 57.0 Hz
56.95 Hz to 57.05 Hz
max. 0.1602 s
Nominal
voltage
Tripping limit
Trip voltages,
conductor-neutral
conductor*
Trip voltages,
conductor-
conductor*
Tripping times
208 V
50%
88%
110%
120%
57.6 V to 62.4 V
103.2 V to 108.0 V
129.6 V to 134.4 V
141.6 V to 146.4 V
99.8 V to 108.2 V
178.9 V to 187.2 V
224.6 V to 233.0 V
245.4 V to 253.8 V
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
240 V
50%
88%
110%
120%
57.6 V to 62.4 V
103.2 V to 108.0 V
129.6 V to 134.4 V
141.6 V to 146.4 V
115.2 V to 124.8 V
206.4 V to 216.0 V
259.2 V to 268.8 V
283.2 V to 292.8 V
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
Name
Brief description
SMA order number
RS485 retrofit kit
RS485 interface
485 USPB-NR
Bluetooth retrofit kit
Bluetooth communication interface
BTPBINV-NR
Replacement varistors
Set with 3 DC varistors
SB-VDC-US01
Ventilation grid
Set with 2 "right and left" ventilation
grids as spare parts
45-7202