51
7 Configuration
7.1 Automatic Line Voltage Detection
The inverter automatically detects the line voltage that it must feed in. Depending on the voltage and
the phase angle between L1-N and L2-N, the inverter determines whether it is connected to a
208 V or 240 V power distribution grid. If the inverter is configured for the wrong grounding system,
the inverter displays an error message.
Limiting values for the voltage and frequency of the AC connection
AC connection
Range limit
AC operating voltage range at 208 V nominal value
183 V to 229 V
AC operating voltage range at 240 V nominal value
211 V to 264 V
AC operating frequency range
59.3 Hz to 60.5 Hz