10  Troubleshooting

SMA America, LLC

68

SB30-40-US-IA-en-34

Installation Manual

Fac-delta+*

Maximum permissible
frequency deviation
above the power
frequency of 60 Hz
before the grid monitoring
disconnects the device
from the power
distribution grid.
The standard value is
optimal for plants
˂ 30 kW.

0 Hz to 4.5 Hz

0.49 Hz

(for the

country

setting USA/

UL1741/

2005)

Fac-MinTripTime* Switch-off time having

fallen below power
frequency.
The standard value is
optimal for plants ˂30 kW.

0.16 s to 300 s

0.16 s

Fan-Test

By setting this parameter
to 1, you can check the
function of the fan.

1

The fan is set to
the maximum
speed.

0

0

Operating
mode: OptiCool

h_total

Total operating hours of
the inverter.
It may be necessary to
change this if you replace
your inverter and want to
use data from the old
device.

0 h to 200,000 h

0 h

Name

Description

Value/range

Explanation

Default

value