3 operating parameters, Operating parameters – SMA SB 3000-US User Manual
Page 66
10 Troubleshooting
SMA America, LLC
66
SB30-40-US-IA-en-34
Installation Manual
10.3 Operating Parameters
Flexible operating parameters
h-Total
Total number of feed-in operation hours
I-dif
Residual current
Iac
Line current
Ipv
DC input current
Max Temperature
Measured maximum temperature at IGBT module
Max Vpv
Maximum DC input voltage
Mode
Current operating mode
Pac
Power fed into the power distribution grid
Power On
Total system start-up counter
Serial Number
Inverter serial number
Temperature
Temperature measured at IGBT module
Vac
Line voltage L1 - L2
Vac L1
Line voltage L1 - N
Vac L2
Line voltage L2 - N
Vfan
Fan voltage
Vpv
DC input voltage
Vpv-PE
DC voltage to ground (for troubleshooting PV ground-faults)
Vpv Setpoint
MPPT DC target voltage
Name
Description
Value/range
Explanation
Default
value
AfciIsOn
Automatic arc-fault
circuit interrupter (AFCI)
yes
yes
no
AntiIsland-Ampl* Amplification of the anti-
island process
0 deg to 10 deg
0 deg
AntiIsland-Freq* Repetition rate of the anti-
island process
0 mHz to
2,000 mHz
500 mHz
Measurement channel
Explanation