10  Troubleshooting

Installation Manual

SB30-40-US-IA-en-34

67

CO2-Fact

The inverter assesses the
yield and displays the
approximate amount of
CO

2

that the inverter has

saved.
The amount of CO

2

is

calculated by multiplying
the generated kWh
(E-total) by the factor
defined in the parameter
"CO2".

0 lb./kWh to 2 lb./

kWh

1.7 lb./kWh

Default

Defines the country
standard for adjusting
country-specific
information. Tip: After
changing one of the
parameters marked with
"*", the parameter
"Default" automatically
changes to adjusted.

USA/UL1741/

2005

USA/

UL1741/

2005

OFF_Grid

NON IEEE1547

E_total

Total energy yield of the
inverter.
It may be necessary to
change this if you replace
your inverter and want to
use data from the old
device.

0 kWh to

200,000 kWh

0 kWh

Fac-delta–*

Maximum permissible
frequency deviation below
the power frequency of
60 Hz before the grid
monitoring disconnects the
device from the power
distribution grid. The
standard value is optimal
for plants ˂ 30 kW.

0.2 Hz to 3.0 Hz

0.69 Hz

(for the

country

setting USA/

UL1741/

2005)

Name

Description

Value/range

Explanation

Default

value