10 Troubleshooting
Installation Manual
SB30-40-US-IA-en-34
67
CO2-Fact
The inverter assesses the
yield and displays the
approximate amount of
CO
2
that the inverter has
saved.
The amount of CO
2
is
calculated by multiplying
the generated kWh
(E-total) by the factor
defined in the parameter
"CO2".
0 lb./kWh to 2 lb./
kWh
1.7 lb./kWh
Default
Defines the country
standard for adjusting
country-specific
information. Tip: After
changing one of the
parameters marked with
"*", the parameter
"Default" automatically
changes to adjusted.
USA/UL1741/
2005
USA/
UL1741/
2005
OFF_Grid
NON IEEE1547
E_total
Total energy yield of the
inverter.
It may be necessary to
change this if you replace
your inverter and want to
use data from the old
device.
0 kWh to
200,000 kWh
0 kWh
Fac-delta–*
Maximum permissible
frequency deviation below
the power frequency of
60 Hz before the grid
monitoring disconnects the
device from the power
distribution grid. The
standard value is optimal
for plants ˂ 30 kW.
0.2 Hz to 3.0 Hz
0.69 Hz
(for the
country
setting USA/
UL1741/
2005)
Name
Description
Value/range
Explanation
Default
value