3 protection devices, 4 dc disconnect, 5 torques and cable sizes – SMA SB 3000-US User Manual
Page 96: Protection devices, Dc disconnect, Torques and cable sizes, 3 protection devices 12.4 dc disconnect
12 Technical Data
SMA America, LLC
96
SB30-40-US-IA-en-34
Installation Manual
12.3 Protection Devices
12.4 DC Disconnect
Specifications subject to change without notice.
12.5 Torques and Cable Sizes
DC reverse polarity protection
Short-circuit diode
AC short-circuit current capability
Software-controlled
AC overcurrent protection
Current-controlled
Grid monitoring (SMA Grid Guard
®
2)
Yes
Maximum DC input current
30 A
Maximum DC short-circuit current
36 A
Maximum system voltage
600 V
Maximum nominal size for string fuses
20 A
Maximum AC operating current
34 A
Dimensions W x H x D
7
7
⁄
8
in. x 12
13
⁄
64
in. x 7
31
⁄
64
in.
(200 mm x 310 mm x 190 mm)
Weight
8 lb. (3.5 kg)
Electronics degree of protection
NEMA 3R
Terminal
Torque
Cable size
AC & DC connecting terminal plate, inverter
15 in-lb. (1.7 Nm)
10 AWG to 6 AWG
(6 mm
2
to 16 mm
2
)
AC & DC connecting terminal plate,
DC Disconnect
15 in-lb. (1.7 Nm)
10 AWG to 6 AWG
(6 mm
2
to 16 mm
2
)
"COMBINED" spring terminal, DC Disconnect
‒
10 AWG to 6 AWG
(6 mm
2
to 16 mm
2
)
Ground terminals PV protective conductor/
DC protective conductor, DC Disconnect
15 in-lb. (1.7 Nm)
10 AWG to 6 AWG
(6 mm
2
to 16 mm
2
)
Screws for attaching the inverter and the
DC Disconnect to the wall mounting bracket and
closing the DC Disconnect cover
44 in-lb. (5 Nm)
‒
Screws for the enclosure lid of the inverter
53 in-lb. (6 Nm)
‒