12  Technical Data

Installation Manual

SB30-40-US-IA-en-34

93

Figure 31: Efficiency curve SB 3800-US-10/3800-US-12

12.1.3 Sunny Boy 4000-US

DC input

Maximum MPP voltage at 208 V nominal value

220 V to 480 V

Maximum MPP voltage at 240 V nominal value

250 V to 480 V

Input operating voltage range

250 V to 600 V

Maximum PV array input power

5,000 W

Maximum DC power

4,300 W

DC starting voltage

285 V

Maximum DC-DC input current

18 A

Maximum short-circuit current

25 A

Maximum backfeed current from the power distribution
grid to the PV array

30 A AC

DC voltage ripple

˂ 10%