3 jumper assignments for grounding systems, Jumper assignments for grounding systems – SMA SB 3000-US User Manual

Page 53

background image

SMA America, LLC

7  Configuration

Installation Manual

SB30-40-US-IA-en-34

53

7.3 Jumper Assignments for Grounding Systems

At the factory, the inverter is configured for connection to the power distribution grid via a neutral
conductor. By setting the jumper, the inverter can be configured for various grounding systems. This
means it is possible to connect the inverter to grounding systems without a neutral conductor
(e.g. to a 240 Delta or 208 Delta).

Figure 23: Pin header for setting the jumper

Possible jumper assignments

Position

Designation

Explanation

A

Pin header

For setting the jumper for various
grounding systems

Jumper assignment

Explanation
Jumper assignment for connection to a 240 V power distribution grid via
a neutral conductor or a 208 V power distribution grid via a neutral
conductor. This setting is configured at the factory.

Jumper assignment for connection to a 208 V power distribution grid
without a neutral conductor.

Jumper assignment for connection to a 240 V power distribution grid
without a neutral conductor.

Jumper assignment for the fan test.