3 jumper assignments for grounding systems, Jumper assignments for grounding systems – SMA SB 3000-US User Manual
Page 53
SMA America, LLC
7 Configuration
Installation Manual
SB30-40-US-IA-en-34
53
7.3 Jumper Assignments for Grounding Systems
At the factory, the inverter is configured for connection to the power distribution grid via a neutral
conductor. By setting the jumper, the inverter can be configured for various grounding systems. This
means it is possible to connect the inverter to grounding systems without a neutral conductor
(e.g. to a 240 Delta or 208 Delta).
Figure 23: Pin header for setting the jumper
Possible jumper assignments
Position
Designation
Explanation
A
Pin header
For setting the jumper for various
grounding systems
Jumper assignment
Explanation
Jumper assignment for connection to a 240 V power distribution grid via
a neutral conductor or a 208 V power distribution grid via a neutral
conductor. This setting is configured at the factory.
Jumper assignment for connection to a 208 V power distribution grid
without a neutral conductor.
Jumper assignment for connection to a 240 V power distribution grid
without a neutral conductor.
Jumper assignment for the fan test.