10  Troubleshooting

SMA America, LLC

70

SB30-40-US-IA-en-34

Installation Manual

T-Start-Fan

Fan turn-on temperature at
minimum speed.

32°F to 212°F

(0°C to 100°C)

122°F

(50°C)

T-Stop

Time during which the
inverter waits before
disconnecting from the
power distribution grid if
"Pac" (fed-in power) falls
below the minimum
required "Vpv-Start"
(DC voltage).

1 s to 1,800 s

2 s

T-Stop-Fan

Fan turn-off temperature

32°F to 212°F

(0°C to 100°C)

122°F

(50°C)

V-Const Setval

DC target voltage for the
operating mode "V-Const".
These parameters are
important only if the
parameter
"Operating Mode" is set to
"V-const".

SB 3000US:

185 V to 500 V

SB 3800-US:

230 V to 600 V

SB 4000US:

230 V to 600 V

SB 3000US:

500 V

SB 3800-US:

600 V

SB 4000US:

600 V

Vac-Min*

The value is used to
calculate the lower limit of
the permissible AC
voltage.
The standard value is
optimal for plants
˂ 30 kW. The standard
value of 12% results in a
trip value of 88%, as the
list of trip limits shows
(see Section 12.6).

0% to 50%

12%

Name

Description

Value/range

Explanation

Default

value