Fixed operating parameters

Vac-Max-Recnet The value is used to

calculate the upper limit
that is required for
reconnecting to the power
distribution grid after a
grid failure.

0% to 20%

5.83%

Vpv-Start

Minimum DC voltage from
which the inverter feeds
into the power distribution
grid.

SB 3000US:

166 V to 480 V

SB 3800-US:

208 V to 580 V

SB 4000US:

208 V to 580 V

SB 3000US:

228 V

SB 3800-US:

285 V

SB 4000US:

285 V

* Changing the parameters can lead to changes regarding compliance with IEEE 1547 and must be approved by the on-

site electric utility company and/or the Authority Having Jurisdiction (AHJ).

Name

Description

Default value

Plimit

Upper limit for AC output power

SB 3000US: 3,050 W
SB 3800-US: 4,050 W
SB 4000US: 4,050 W

SMA-SN

Inverter serial number

Software-BFR

Firmware version of the operation control unit

Software-SRR

Firmware version of the current controlling unit