C-max – SMA SB 3000-US User Manual
Page 72
10 Troubleshooting
SMA America, LLC
72
SB30-40-US-IA-en-34
Installation Manual
Fixed operating parameters
Vac-Max-Recnet The value is used to
calculate the upper limit
that is required for
reconnecting to the power
distribution grid after a
grid failure.
0% to 20%
5.83%
Vpv-Start
Minimum DC voltage from
which the inverter feeds
into the power distribution
grid.
SB 3000US:
166 V to 480 V
SB 3800-US:
208 V to 580 V
SB 4000US:
208 V to 580 V
SB 3000US:
228 V
SB 3800-US:
285 V
SB 4000US:
285 V
* Changing the parameters can lead to changes regarding compliance with IEEE 1547 and must be approved by the on-
site electric utility company and/or the Authority Having Jurisdiction (AHJ).
Name
Description
Default value
Plimit
Upper limit for AC output power
SB 3000US: 3,050 W
SB 3800-US: 4,050 W
SB 4000US: 4,050 W
SMA-SN
Inverter serial number
Software-BFR
Firmware version of the operation control unit
Software-SRR
Firmware version of the current controlling unit
Name
Description
Value/range
Explanation
Default
value