10  Troubleshooting

Installation Manual

SB30-40-US-IA-en-34

69

Memory Function

no function

no function

Default param.

Sets all
parameters to
the standard
value.

Reset Op.Data

Sets all
parameters that
are visible on
the user level to
the standard
values.

Reset errors

Resets all
permanent
errors that lead
to device
disconnection.

Operating Mode Operating modes of an

inverter

MPP-Operation Sets the inverter

to the operating
mode "MPP"

MPP

Turbine

Sets the inverter
to the operating
mode "Turbine"

V-const

Sets the inverter
to the operating
mode "V-Const"

Stop

Disconnection
from the power
distribution grid,
no operation

T-Max-Fan

Temperature at which the
fan reaches the maximum
fan speed.

32°F to 212°F

(0°C to 100°C)

194°F

(90°C)

T-Start

Gird monitoring time:
Time during which the
inverter monitors the
power distribution grid
before connecting.
This value defaults to
5 minutes after a grid fault.

5 s to 1,600 s

10 s

Name

Description

Value/range

Explanation

Default

value