10  Troubleshooting

SMA America, LLC

64

SB30-40-US-IA-en-34

Installation Manual

B

Red LED

Glowing

Tripped ground fuse
Ground fuse was tripped or is not available.
Corrective measures:

• Check the PV plant for ground-faults

(see Section 11.6).

C

Yellow LED

Glowing

Control System Fault
The operation of the inverter is permanently
inhibited. The inverter no longer feeds into the
power distribution grid.

Blinking

AFCI self-test
The inverter is carrying out the AFCI self-test.

Glows for 5 s,
goes out for 3 s,
blinks twice

Grid failure
This blink code can be caused by any of the
following conditions:

• Grid undervoltage
• Grid overvoltage
• Grid underfrequency
• Grid overfrequency
• Sudden change in the power frequency

or the line voltage

Corrective measures:

• Monitor the status of the power

distribution grid at the AC connecting
terminal plate of the DC Disconnect and
the AC miniature circuit-breaker
between the inverter and the power
distribution grid.

Position

Designation

Status

Explanation