10  Troubleshooting

Installation Manual

SB30-40-US-IA-en-34

75

Fac-Bfr, Fac-Srr

The AC power frequency exceeds the permissible range. To prevent
islanding, the inverter disconnects from the power distribution grid.
Corrective measures:

• Ensure that the AC cable is correctly connected (see Section 6.3).
• Ensure that the power frequency is within the permissible range.
• If the power frequency is within the permissible range and this

message continues to be displayed, contact SMA Service Line (see
Section 15).

GFDI Fuse Open

The ground fuse has tripped.
Corrective measures:

• Check the PV plant for ground-faults (see Section 11.6).
• Replace the ground fuse (see Section 11.7).

Grid-Timeout,
Grid-Fault-S

The grounding system of the power distribution grid could not be detected.
Corrective measures:

• Contact the SMA Service Line (see Section 15).

Imax

Overcurrent detected on AC side.
The current to the power distribution grid exceeds the specifications. This
may be caused by a serious system incident.
Corrective measures:

• Ensure that the PV plant is correctly rated.
• Ensure that the grid conditions are maintained.

K1-Close

An internal test has failed.
Corrective measures:

• Contact the SMA Service Line (see Section 15).

K1-Open, K2-Open

MSD-FAC, MSD-Idif

An internal measurement comparison fault has been detected.
The measured values of both processes (OCU and current controlling unit)
deviate too much from one another.
Corrective measures:

• Contact the SMA Service Line (see Section 15).

MSD-VAC

OFFSET

Grid monitoring self-test failed.
Corrective measures:

• If the message occurs frequently, contact the SMA Service Line

(see Section 15).

Message

Cause and corrective measures