beautypg.com

3 protective devices – SMA STP 12000TL-US User Manual

Page 73

background image

Storage temperature

−40°C to +60°C

(−40°F to +140°F)

Maximum permissible value for relative humid-
ity, non-condensing

100%

Maximum operating altitude above mean sea
level

2,000 m (6,562 ft)

Typical noise emission

≤ 51 dB(A)

Power loss in night mode

< 1.8 W

Maximum data volume per inverter with Speed-
wire/Webconnect

550 MB/month

Additional data volume when using the Sun-
ny Portal live interface

600 kB/hour

Topology

Transformerless

Cooling method

OptiCool: temperature-controlled fan

Enclosure type rating in accordance with UL50

Type 3R

Protection class

I

Grid configurations

480 V / 277 V WYE

Approvals and national standards, as per
05/2013

UL1741

CAN/CSA C22.2 No. 107.1-01

14.3 Protective Devices

DC reverse polarity protection

Short-circuit diode

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 3

Maximum permissible fuse protection

50 A

Ground-fault monitoring STP 12000TL-US-10

Insulation monitoring: R

iso

 > 417 kΩ

Ground-fault monitoring STP 15000TL-US-10

Insulation monitoring: R

iso

 > 333 kΩ

Ground-fault monitoring STP 20000TL-US-10

Insulation monitoring: R

iso

 > 250 kΩ

Ground-fault monitoring STP 24000TL-US-10

Insulation monitoring: R

iso

 > 208 kΩ

All-pole sensitive residual-current monitoring unit

Available

Arc fault detection AFCI, type 1, listed accord-
ing to UL1699B

Available

14 Technical Data

SMA Solar Technology AG

Installation Manual

73

STP12-24TL-US-IA-en-16

This manual is related to the following products: