STP 24000TL-US-10

Maximum residual output current

142.5 A

pk

Duration of the maximum residual output current

0.0131 s

Line synchronization characteristics / In-rush current

Method 2

Rated power frequency

60 Hz

Operating range at AC power frequency 60 Hz

59.3 Hz to 60.5 Hz

Maximum utility backfeed current to utility

Limits of accuracy of voltage measurement

2%

Limits of accuracy of frequency measurement

±0.1 Hz

Limits of accuracy of time measurement at nominal trip
time

±0.1%

Output power at +60°C (+140°F)

17,000 W

Maximum power operating ambient temperature

+45°C (+113°F)

Power factor at rated power

1

Displacement power factor, adjustable

0

overexcited

to 0

underexcited

Feed-in phases

3

Connection phases

3

Overvoltage category in accordance with UL1741

IV

Efficiency

STP 24000TL-US-10

Maximum efficiency, η

max

98.5%

CEC efficiency, η

CEC

98.0%

14.2 General Data

Width x height x depth

665 mm x 650 mm x 265 mm

(26.18 in x 25.59 in x 10.43 in)

Weight

55 kg (121 lb)

Length x width x height of the packaging

780 mm x 380 mm x 790 mm

(30.71 in x 14.96 in x 31.10 in)

Transport weight

61 kg (134.5 lb)

Operating temperature range

−25°C to +60°C

(−13°F to +140°F)

14 Technical Data

SMA Solar Technology AG

Installation Manual

STP12-24TL-US-IA-en-16

72