STP 20000TL-

US-10

Total harmonic distortion of the output
current with total harmonic distortion
of the AC voltage < 2%, and AC
power > 50% of the rated power

≤ 3%

≤ 3%

≤ 3%

Maximum residual output current

142.5 A

pk

142.5 A

pk

142.5 A

pk

Duration of the maximum residual out-
put current

0.0131 s

0.0131 s

0.0131 s

Line synchronization characteristics /
In-rush current

Method 2

Method 2

Method 2

Rated power frequency

60 Hz

60 Hz

60 Hz

Operating range at AC power fre-
quency 60 Hz

59.3 Hz to

60.5 Hz

59.3 Hz to

60.5 Hz

59.3 Hz to

60.5 Hz

Maximum utility backfeed current to
utility

Limits of accuracy of voltage measure-
ment

2%

2%

2%

Limits of accuracy of frequency mea-
surement

±0.1 Hz

±0.1 Hz

±0.1 Hz

Limits of accuracy of time measure-
ment at nominal trip time

±0.1%

±0.1%

±0.1%

Output power at +60°C (+140°F)

12,000 W

15,000 W

17,000 W

Maximum power operating ambient
temperature

+45°C (+113°F) +45°C (+113°F) +45°C (+113°F)

Power factor at rated power

1

1

1

Displacement power factor, adjustable

0

overexcited

to 0

underexcited

0

overexcited

to 0

underexcited

0

overexcited

to 0

underexcited

Feed-in phases

3

3

3

Connection phases

3

3

3

Overvoltage category in accordance
with UL1741

IV

IV

IV