Damage to the inverter due to moisture ingress during electrical installation

• Never open the inverter when it is raining or snowing, or the humidity is over 95%.
• For attaching the conduits to the enclosure, only use UL-listed rain-tight conduit fittings or UL-

listed conduit fittings for wet locations complying with UL514B.

• Seal all unused openings tightly.

Ground faults, unreliable and highly resistive connections due to Wire Nuts

®

Potential damage to or failure of the inverter.

• Do not use Wire Nuts

®

.

Electrical installations
All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code

®

ANSI/NFPA 70 or the Canadian Electrical Code

®

CSA C22.1.

• Before connecting the inverter to the utility grid, contact your local grid operator. The

electrical connection of the inverter must be carried out by qualified persons only.

• Ensure that no cables used for electrical connection are damaged.