Interior View

Figure 6: Connection areas in the interior of the inverter

Position

Designation

A

Connecting terminal plate for AC connection

B

Switch for changing the language to English for service purposes

C

Screw to release and attach the communication board

D

Slot for the SD memory card, for service purposes only

E

Terminal for equipment grounding and grounding electrode conductor

F

Connecting terminal plate for DC connection

6.3

AC Connection

6.3.1

Requirements for the AC Connection

Additionally required material (not included in the scope of delivery):

☐ 1 metal conduit: 25.4 mm (1 in)
☐ 1 UL-listed rain-tight conduit fitting for wet locations: 25.4 mm (1 in)

Cable requirements:

☐ The AC cable must be approved for temperatures of over +90°C (+194°F).
☐ The AC cable must be designed in accordance with the local installation requirements.
☐ The AC cable must be made of solid wire or stranded wires.
☐ Conductor cross-section: 10 mm² to 16 mm² (8 AWG to 6 AWG)
☐ Cable type: copper wire
☐ The maximum cable length subject to conductor cross-section must be observed.