beautypg.com

SMA STP 12000TL-US User Manual

Page 40

background image

Name

Value/range

Default value

Voltage monitoring upper minimum threshold (Un-
dervoltage/Slow)

138.5 V to 277.0 V

243.8 V

Voltage monitoring of median minimum threshold
(Undervoltage/Fast)

138.5 V to 277.0 V

138.5 V

Voltage monitoring median max. threshold trip.time
(Overvoltage/Fast, maximum time)

0.1 s to 6,000 s

0.16 s

Voltage monitoring lower max. threshold trip. time
(Overvoltage/Slow, maximum time)

0.1 s to 6,000 s

1.0 s

Voltage monitoring upper min. threshold trip. time
(Undervoltage/Slow, maximum time)

0.1 s to 1,000 s

2.0 s

Voltage monitoring median min. threshold trip.time
(Undervoltage/Fast, maximum time)

0.1 s to 1,000 s

0.16 s

Frequency monitoring lower maximum threshold
(Overfrequency)

50 Hz to 65 Hz

60.5 Hz

Frequency monitoring upper minimum threshold
(Underfrequency)

44 Hz to 60 Hz

59.3 Hz

Frq. monitoring lower max. threshold trip. time
(Overfrequency, maximum time)

0.1 s to 9,000 s

0.16 s

Frq. monitoring upper min. threshold trip. time (Un-
derfrequency, maximum time)

0.1 s to 30,000 s

0.16 s

8 Configuration

SMA Solar Technology AG

Installation Manual

STP12-24TL-US-IA-en-16

40

This manual is related to the following products: