5

Mounting

5.1

Requirements for Mounting

Requirements for the mounting location:

Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.

• Do not mount the inverter in areas containing highly flammable materials or gases.
• Do not mount the inverter in a potentially explosive atmosphere.

☐ Do not mount the inverter on a pillar.
☐ The inverter must be mounted on a solid support surface (e.g. concrete, brickwork, free-

standing constructions).

☐ Do not install the inverter in a living area.
☐ The mounting location must be suitable for the weight and dimensions of the inverter (see

Section 14 "Technical Data", page 69).

☐ To ensure optimum operation, the ambient temperature should be between -25°C (-13°F) and

60°C (140°F).

☐ The inverter can be mounted in a position that is directly exposed to solar irradiation.

However, it is possible that the inverter may become overheated and its power be reduced as
a result.

☐ Climatic conditions must be met (see Section 14 "Technical Data", page 69).
☐ The mounting location should be freely and safely accessible at all times without the need for

any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.

5 Mounting

SMA Solar Technology AG

Installation Manual

19

STP12-24TL-US-IA-en-16