4 checking the function of the fans, 5 checking the pv system for ground faults – SMA STP 12000TL-US User Manual
Page 57
• Reinsert the ventilation grid until it snaps
into place.
• Turn the rotary lock of the ventilation grid
with a flat-blade screwdriver until the slot is
in a horizontal position and the arrows
point to the right.
• Ensure that the ventilation grid is securely in place.
12. Recommission the inverter (see Section 11, page 61).
13. Check the fans to ensure that they are working properly (see Section 10.4, page 57).
10.4 Checking the Function of the Fans
You can check the function of the fans by setting a parameter.
The basic procedure for changing operating parameters is described in the manual of the inverter
or the communication product (see the operating manual of the inverter or communication product).
Procedure:
1. Select the parameter Fan test or FanTst and set to On.
2. Save settings.
3. Check whether air is being drawn in through the bottom and is coming out of the upper
ventilation grids and whether the fans are making any unusual noises.
If no air is being drawn in through the bottom, no air is coming out of the ventilation grids, or
the fans are making unusual noises, then the fans were presumably installed improperly.
Check whether the fans have been installed correctly.
If the fans were installed correctly, contact Service (see Section 17, page 77).
4. Select the parameter Fan test or FanTst and set to Off.
5. Save settings.
10.5 Checking the PV System for Ground Faults
If the red LED is glowing and the and the event number 3501, 3601 or 3701 is displayed in the
comunication product (e.g. Sunny Portal), this could indicate a ground fault. The electrical insulation
from the PV system to ground is defective or insufficient.