beautypg.com

8 scaling function parameters, 1 measuring units per revolution, Table 38 measuring units per revolution – HEIDENHAIN PROFINET User Manual

Page 74: Scaling function parameters, Measuring units per revolution, Table 38

background image

Functional description of the encoder

74

Note: If scaling is used the preset function shall be used after

the scaling function to ensure that the preset value is
entered in the current measuring unit.


Note: There is no preset activated when the preset value is

written to the encoder. The preset function is controlled
by bits in the control and status words (G1_STW and
G1_ZSW) and bit in the operating parameters. The pre-
set value is used when a preset is requested by bit 12
in the control word (G1_STW).

7.8

Scaling function parameters

The scaling function converts the encoder’s physical absolute po-

sition value by means of software in order to change the resolu-

tion of the encoder. The scaling parameters will only be activated

if the parameter Class 4 functionality and Scaling function control

are enabled. The permissible value range for the scaling is limited

by the resolution of the encoder. The scaling parameters are se-

curely stored in the IO controller and are reloaded into the encod-

er at each power-up.

7.8.1

Measuring units per revolution

This parameter sets the single turn resolution of the encoder. In

other words it is the number of different measuring steps during

one revolution of the encoder.

Example:

For a 13-bit encoder with a single turn resolution of 13 bits the

permissible value range for "Measuring units per revolution" is be-

tween 2

0

and 2

13

(8192).

Parameter

Meaning

Data type

Measuring units

per revolution

The single turn resolution

in measuring steps

Unsigned 32

Measuring units

per revolution

64 bit

The single turn resolution

in measuring steps for en-

coders with a resolution

exceeding 32 bits.

Unsigned 64

Table 40

Measuring units per revolution

Note: After downloading new scaling parameters, the preset

function must be used to set the encoder starting
point to absolute position 0 or to any required starting
position within the scaled operating range.