Encoder state machine
107
10.1
Normal operation state
If using encoder complying with encoder profile v4.1, then bit 10
Control by PLC in Control word 2 needs to be set before the data
in Control word is valid. If not set, Control word is not used by the
10.1.2
Profile version 3.x
If using encoders complying with encoder profile 3.x, the data in
Control word is always valid and bit 9 Control requested in Status
10.1.3
Profile version 3.x and 4.x
When using telegram 81-83 and Control word bit 13 Request ab-
solute value cyclically is set, then Status word bit 13 Transmit ab-
solute value cyclically is set. Status word bit 13 is cleared (bit
13=0) when Control word bit 13 is cleared. Status word bit 13 is
always cleared, when using telegram 84 due to the fact that no
absolute value is sent in G1_XIST2.
10.2
Parking state
This state can be reached from any other state. The position value
in G1_XIST1, G1_XIST2 and G1_XIST3 are set to zero. Errors are
cleared and alarms are disabled in parking mode.
10.3
Set/shift home position (Preset)
The Set/shift home position is initiated when Control word bit 12
Request set/shift of home position is set. In this case the Status
word bit 12 Set/shift of home position executed is set to 1. In or-
der to initiate a set/shift home position Class 4 functionality must
be enabled otherwise there will be an error in G1_XIST2.