Encoder and Gateway functionality, DPV0

51

5.6.9

Warnings

Warnings indicate that tolerances for certain internal parameters

of the device have been exceeded. Contrary to alarms, no faulty

position values are expected in case of warnings. Octets 20 and

21 of the diagnostic function indicate the status of the warnings.

If a warning is set, the Ext_Diag bit in the diagnostic function is

logically set to 1 until the warning is cleared. All warnings are

deleted when the diagnostic message of the device has been

read. However, if the tolerances are still exceeded, the warning is

activated again. The warning “Maximum operating time exceeded”

(bit 4) is not activated before the system is switched on again.


Note:

Not every encoder supports every warning.
Please refer to the diagnostic information under
“Supported Warnings”, see chapter 5.6.10, for
information on the support of specific warnings.


Octet

20

21

Bits

15-8

7-0

Warnings

Octet

Definition

=0

=1

0

Frequency exceeded

No

Yes

1

Temperature exceeded

No

Yes

2

Light control reserve

Not reached

Reached

3

CPU monitoring status

OK

Reset

4

Maximum operating time

exceeded

No

Yes

5

Battery charging

OK

Too low

6

Reference point

Reached

Not reached

7..15

Currently not assigned

Table 29

Diagnostics, warnings